General Information
Schneider Electric Ac Current Relays EOCR – SSD
Digital Overload Relays Relays
- MCU( Microprocessor Control Unit ) Based/2-CT Type
- Real Time Processing/Higher Preceision
- Current Setting Range 05Type:0.5~6A/30Type:3~30A/60Type:10~60A
- Indicating real current on the display
- Trip cause digital display for easy trouble shooting
- Reset:Manual(instantaneous)/Electrical(remote)
- Load selection by DIP switch:Single phase(1P)/Three phase(3P)
- Fail-safe(N)/Non-Fail-safe(R)

Technical Information
Model SSD Technical Specs
Protection
Protective Item | Trip Time | Descrption |
Over-current | O-TIME | |
Phase Loss | 3 sec | |
Locked Rotor | 0.5sec after elapse of dt | 2times OC setting value |
Specification
Current Setting Range | Current | 05 | 0.5 ~ 6A |
30 | 3.0 ~ 30A | ||
60 | 10 ~ 60A | ||
Starting delay time | D-TIME | OFF | |
Trip time | O-TIME | 0.5, 1~10 sec | |
Operating t-c characteristic | Over-Current | Definite | |
Tolerance | Current | ±5% | |
TIME | ±5% | ||
Environment | Temperature | Operation | -20 ~60℃ |
Store | -30 ~80℃ | ||
Humidity | 30~85% RH Non-condensing | ||
Control Power | 220 : 220VAC±15%, 50/60Hz | ||
110 : 110VAC ±15%, 50/60Hz | |||
Output relay | 2-SPST | 3A / 250VAC Resistive | |
Insulation | Between casing and circuit | Over 10MΩ, 500VDC | |
Dielectric Strenghth | Between casing and circuit | 2000VAC 60Hz, 1min | |
Between open contacts | 1000VAC 60Hz, 1min | ||
between circuit | 2000VAC 60Hz, 1min | ||
Reset | Manual/Electrical | ||
Installation | 35mm DIN-Rail or Panel Munting | ||
Document
Other Features
–